Price:
European delivery - 30 working days, other countries +7 working days.
Ask a question about this item
Ask a question about this item
DZD ATEX GAS and HYDROGEN – explosion-proof axial roof fans for explosive gas and hydrogen atmospheres, ≤6510 m³/h
DZD Ex e axial roof fans with horizontal air discharge are designed for potentially explosive gas and hydrogen atmospheres classified as Zones 1 and 2. The fans comply with ATEX Directive 2014/34/EU and have ATEX and IECEx approvals.
The fans are suitable for gases and vapours in groups IIA and IIB, including hydrogen (IIB+H₂). The maximum airflow capacity of the series is 6510 m³/h.
The operating temperature range for DZD 50/6 is not specified separately in the catalogue description.
DZD ATEX GAS and HYDROGEN – technical catalogue (PDF)
The accessories are not included in the fan type examination certificate. Contact the manufacturer's technical and sales department for alternative construction solutions.
All dimensions are in millimetres (mm), weights in kilograms (kg). Weights are approximate.
| Model | A | ØB | C | ØD | ØE | F | ØG | ØH | I | kg |
| DZD Ex e 250 | 500 | 570 | 285 | 355 | 560 | 170 | 263 | 286 | 7 | 14 |
| DZD Ex e 300 | 570 | 660 | 335 | 405 | 630 | 190 | 313 | 356 | 9 | 20 |
| DZD Ex e 355 | 610 | 720 | 340 | 455 | 670 | 190 | 363 | 395 | 9 | 24 |
| DZD Ex e 400 | 650 | 830 | 375 | 505 | 710 | 190 | 413 | 438 | 9 | 27 |
| DZD Ex e 500 | 800 | 940 | 380 | 605 | 860 | 190 | 513 | 541 | 9 | 39 |
| DZD Ex e 600 | 840 | 1100 | 420 | 720 | 900 | 190 | 613 | 674 | 11 | 43 |

The DZD Ex e series is designed for potentially explosive atmospheres containing gases and vapours of groups IIA and IIB, including hydrogen. The series comprises 13 models with maximum airflow capacity up to 6510 m³/h.
| Code | Model | Motor | Poles | Pm (kW) | In (A) | IP / class | Q max (m³/h) | LwA5 (dB(A)) |
| 1DZ2521 | DZD 25/4 B Ex e | T | 4 | 0.038 | 0.19 | 64/F | 800 | 68 |
| 1DZ2524 | DZD 25/2 B Ex e | T | 2 | 0.14 | 0.39 | 64/F | 1600 | 87 |
| 1DZ3026 | DZD 30/6 B Ex e | T | 6 | 0.025 | 0.12 | 64/F | 940 | 64 |
| 1DZ3027 | DZD 30/4 B Ex e | T | 4 | 0.095 | 0.48 | 64/F | 1390 | 74 |
| 1DZ3028 | DZD 30/2 B Ex e | T | 2 | 0.3 | 0.87 | 64/F | 2690 | 91 |
| 1DZ3542 | DZD 35/6 B Ex e | T | 6 | 0.04 | 0.13 | 64/F | 1370 | 69 |
| 1DZ3543 | DZD 35/4 B Ex e | T | 4 | 0.13 | 0.49 | 64/F | 2060 | 77 |
| 1DZ3544 | DZD 35/2 B Ex e | T | 2 | 0.62 | 1.91 | 64/F | 4280 | 97 |
| 1DZ4543 | DZD 40/6 B Ex e | T | 6 | 0.1 | 0.53 | 64/F | 2130 | 74 |
| 1DZ4544 | DZD 40/4 B Ex e | T | 4 | 0.17 | 0.70 | 64/F | 3200 | 84 |
| 1DZ5061 | DZD 50/6 B Ex e | T | 6 | 0.18 | 0.65 | 64/F | 3870 | 77 |
| 1DZ5062 | DZD 50/4 B Ex e | T | 4 | 0.485 | 1.70 | 64/F | 5830 | 88 |
| 1DZ6061 | DZD 60/6 B Ex e | T | 6 | 0.365 | 1.08 | 64/F | 6510 | 83 |
T – three-phase motor; Pm – motor power; In – rated current; Q max – maximum airflow; LwA5 – sound power level with free inlet. The specific fan supply voltage is not stated in the catalogue performance tables.
The operating temperature range for DZD 50/6 is not specified separately in the catalogue description.
DZD Ex e explosion-proof axial roof fans are intended for installation on building roofs, with horizontal air discharge. They are suitable for potentially explosive gas and hydrogen atmospheres classified as Zones 1 and 2, in accordance with their ATEX and IECEx markings.
The mounting base must be selected according to the roof construction and the dimensions of the specific fan. The manufacturer offers SO bases for flat roofs, SOWT bases for corrugated and trapezoidal roofs and SDS bases for pitched roofs. SD silencers, SZ intermediate bases, ELA Ex flexible connections and SG safety grilles may be used where required.
The fans use three-phase asynchronous motors with integrated PTC thermistors for temperature monitoring. The manufacturer recommends MVS 6 or TMS thermistor protection devices for motor thermal protection. These devices must be installed outside potentially explosive areas.
Fan speed can be controlled using TR transformers, except for the DZD 35/2 B Ex e model. The fans can operate in reverse mode, but airflow is reduced by approximately 35% when the direction is reversed.
Detailed information on fan construction, operating conditions, dimensions, electrical protection and mounting accessories is provided in the manufacturer's technical catalogue.
DZD ATEX GAS and HYDROGEN – technical catalogue and installation information (PDF)