Price:
| * Price / AXC: |
Select
|
| Price / SAP sealing clamp: |
Select
|
| Price / APG vent guard: |
Select
|
| Speed controller: |
Select
|
EU shipping 14 working days, non EU 21 working days
Ask a question about this item
Ask a question about this item
AXC TP - exceptionally quiet and efficient centrifugal in-line fans ≤450 m³/h
AXC TP – centrifugal inline duct fans for Ø100–160 mm ducts, airflow up to 450 m³/h, pressure up to 325 Pa. This inline duct fan: casing of self-extinguishing, non-flammable technopolymer, centrifugal impeller with backward curved blades, ball bearing motor. Sound level from 32 dB(A) at 3 m, so it is a silent duct fan.


For extracting air from bathrooms, kitchens, toilets, offices and other residential, commercial or public premises. The centrifugal impeller generates high pressure, so these inline duct fans suit longer and more complex duct systems where one fan serves several rooms. As a duct fan for a cooker hood, AXC TP may only be used with filters installed upstream that clean the greasy air.
The duct fan is installed in a circular duct. Sealing clamps are recommended to reduce vibration transfer to the ducts. If no duct is connected to the outlet, a protective grille APG must be fitted. Recommended transformer speed controllers: RVS 0.5 A (AXC 100–160 TP). Dimensions are in the dimensions tab.
AXC TP fans are made for Ø100, Ø125, Ø150 and Ø160 mm ducts. For example: AXC 100 TP – 211 m³/h, 32 dB(A); AXC 125 TP – 265 m³/h, 33 dB(A); AXC 160 TP – 450 m³/h, 325 Pa. Full data is in the technical information tab.
| Code |
A
|
B
|
ØC
|
ØD |
| AXC 100 TP | 238 | 25 | 98 | 212 |
| AXC 125 TP | 238 | 25 | 123 | 212 |
| AXC 150 TP | 232 | 28 | 147 | 253 |
| AXC 160 TP | 232 | 28 | 157 | 253 |

| Code | Motor | m³/h | l/s | Pa | W | A | dB(A)* | kg |
| AXC 100 TP | AC | 211 | 58 | 263 | 27 | 0.13 | 32 | 1.5 |
| AXC 125 TP | AC | 265 | 73 | 251 | 27 | 0.13 | 33 | 1.5 |
| AXC 150 TP | AC | 430 | 119 | 325 | 65 | 0.29 | 39 | 2 |
| AXC 160 TP | AC | 450 | 125 | 325 | 65 | 0.29 | 40 | 2 |
*LpA, measured at 3 m in open field 230V-50 Hz
Speed controller:
| AXC 100-160 TP |
| 5 step, transformer RVS - 0.5 A |
![]() |
Pressure loss curves

You might also like: