Catalog
Catalogue
SEARCH
    • Price:

SEARCH
Attention!
In the time of quarantine we will work as usual. Please place orders in the system, it will be prepared to pick up outside or delivered by courier.
 

 

European delivery - 30 days, other countries +7 days.

Ask a question about this item

Ask a question about this item

Explosion proof axial fans AVWOSE EX-ATEX ≤11000m³/h

  • AVWOSE EX-ATEX explosion-proof axial fans designed to convey vapor or gas directly outside from commercial, industrial and other premises where there is a high risk of explosion due to explosive or flammable gas
  • complies with ATEX directive
  • AVWOSE 2G - fans intended for operation in Z1 (1) and Z2 (2) gas explosion zones are identified by the following symbols:

  • temperature class: T1 to T3 (special order T4)
  • explosion group: II (Subgroups IIA and IIB)
  • fans not fitted for speed control
  • maximum ambient temperature 40 °C
  • AVWOSE 3G / 3D - fans designed to operate in the Z2 (2) and Z22 (22) gas and dust explosion areas are identified by the following symbols:

  • temperature class: T1 to T3
  • maximum dust surface temperature up to 120 °C
  • maximum ambient temperature 40 °C
  • gas explosion group: IIA and IIB
  • dust explosion group: IIIB
  • fans adapted for speed control by a special frequency converter
  • temperature sensors (3xPTC 155C) mounted on the fan motor should be connected to an EC certified relay to ensure proper motor protection during control
  • explosion-proof fans for zone Z1 (1) with frequency converter can be ordered on request
  • the reverse is available on request for all models
  • fan housing made of galvanized steel, powder or antistatic coated (depending on model)
  • axial impeller made of special antistatic material
  • all models with three-phase, explosion-proof electric motors, protection class IP55
  • motor side hot galvanized or powder coated, impeller side mesh available on request
  • manufactured under Directive 8/37/EC - Machinery Safety, Directive 94/9/EC (ATEX) - Equipment and protective systems in potentially explosive atmospheres
  • marking of zones:
  • Z1 - zone in which, under normal conditions of use, a vapor or gas mixture may be formed
  • Z2 - zone with low probability of explosive gas mixture, explosive mixture may only be present for a short time
  • Z22 - area with low probability of formation of explosive dust mixture, ie. transient, for example, during a fault
  • 1 year warranty
Code
A
B
ØD
C
D
AVWOSE-31 140 300 315 360 410
AVWOSE-35 140 310 355 400 490
AVWOSE-40 140 340 400 490 530
AVWOSE-45 140 390 450 520 580
AVWOSE-50 140 400 500 560 610
AVWOSE-56 190 400 560 620 700

 

 

Code AVWOSE
Phase
Voltage, V at 50Hz
Capacity, m³/h
Pressure, Pa
Power, W Noise level, dB(A)4m Speed, min-1
25 III 400 900 40 120 52 1400
25 3G/3D III 400 900 40 120 52 1400
31 M III 400 1790 35 180 54 900
31 M 3G/3D III 400 1790 35 180 54 900
31 D III 400 2808 80 250 56 1400
31 D 3G/3D III 400 2808 80 250 56 1400
35 M III 400 2890 50 180 57 900
35 M 3G/3D III 400 2890 50 180 57 900
35 D III 400 4530 123 250 60 1400
35 D 3G/3D III 400 4530 123 250 60 1400
40 M III 400 3890 52 180 59 900
40 M 3G/3D III 400 3890 52 180 59 900
40 D III 400 6084 128 250 62 1400
40 D 3G/3D III 400 6084 128 250 62 1400
45 M III 400 4700 53 180 61 900
45 M 3G/3D III 400 4700 53 180 61 900
45 D III 400 7350 129 370 67 1400
45 D 3G/3D III 400 7350 129 370 67 1400
50 M III 400 6120 57 180 63 900
50 M 3G/3D III 400 6120 57 180 63 900
50 S III 400 8820 138 370 68 1400
50 S 3G/3D III 400 8820 138 370 68 1400
50 D III 400 9900 138 550 75 1400
50 D 3G/3D III 400 9900 138 550 75 1400
56 S III 400 11000 150 550 77 1400
56 S 3G/3D III 400 11000 150 550 77 1400
56 M III 400 7040 62 370 67 900
56 M 3G/3D III 400 7040 62 370 67 900

 

Pressure loss diagrams