Price:
| Protection level | Equipment category (gases) | Zone of use (gases) | Equipment category (dusts) | Zone of use (dusts) | Hazard level of operating zone | In our product range |
| Very high |
1G
|
Zone 0
|
1D
|
Zone 20
|
Explosive atmosphere is always present |
No
|
| High |
2G
|
Zone 1
|
2D
|
Zone 21
|
Explosive atmosphere is likely |
Yes
|
| Normal |
3G
|
Zone 2
|
3D
|
Zone 22
|
Explosive atmosphere is unlikely | Yes |
| Table No. 1 | |
| ATEX installation zone |
Zone 1 / 21 / 2 / 22
|
| ATEX zone inside the fan |
Zone 1 / 21 / 2 / 22
|
| Equipment group |
II
|
| Equipment category |
2G / 2D / 3G / 3D
|
| Equipment Protection Level (EPL) |
b / c
|
| Electric motor protection type |
Ex-d Gb / Ex-de Gb / Ex-e Gb / Ex-nA Gc / Ex-tb Db / Ex-tc Dc
|
| Gas temperature class |
T3 / T4 / T5 / T6
|
| Gas group |
IIA / IIB / IIB + H₂
|
| Dust group |
IIIA / IIIB / IIIC
|
| IP protection class |
IP55 / IP64 / IP65 / IP66
|
| Standard temperature range |
–20 °C / +60 °C (–40 °C on special request)
|
| Notified body |
IMQ (0051) / TÜV NORD (0044) / TÜV SÜD (0123) / TÜV AUSTRIA (0408) / BV/EPS (2004)
|
| Table No. 2 | |
| ATEX installation zone |
Zone 2 / 22
|
| ATEX zone inside the fan |
Zone 2 / 22
|
| Equipment group |
II
|
| Equipment category |
3G / 3D
|
| Equipment Protection Level (EPL) |
b / c
|
| Electric motor protection type |
Ex-d Gb / Ex-de Gb / Ex-e Gb / Ex-nA Gc / Ex-tb Db / Ex-tc Dc
|
| Gas temperature class |
T3 / T4 / T5 / T6
|
| Gas group |
IIA / IIB / IIB + H₂
|
| Dust group |
IIIA / IIIB / IIIC
|
| IP protection class |
IP55 / IP65
|
| Standard temperature range |
–20 °C / +40 °C
|